Zirkoninpolku 2
KLA Talotekniikka Oy hired us to check the airtightness of the ventilation ducts in the new buildings at Kivistö Residential Block. We had to follow the Finnish Building Regulation Collection D2/2012 requirements and guidelines for duct tightness.

Tarkastus
KLA Talotekniikka Oy
Vantaa
2019
KLA Talotekniikka Oy commissioned an inspection of the airtightness of ventilation ducts in the Kivistö Residential Block new construction project. The airtightness of the ducts had to comply with the Finnish Building Code, Section D2/2012, regulations, and guidelines.
Test procedure and airtightness requirements
• Encased supply and exhaust units were pressure tested at 500 Pa, with a maximum allowable leakage of 1.8 l/s·m² (Class A).
• Class B ducts were pressure tested at 400 Pa, with a maximum allowable leakage of 0.45 l/s·m² (Class B).
• Class C ducts were pressure tested at 500 Pa, with a maximum allowable leakage of 0.18 l/s·m² (Class C).
The inspection followed SFS 4699 standards and D2 section 3.7.1 guidelines. According to regulations, a ventilation system is considered sufficiently airtight when it meets at least airtightness Class B.
Airtightness classifications:
Class A:
✔ Ducts visible in ventilated rooms
✔ Pressure difference to the room < 150 Pa
Class B:
✔ Ducts outside ventilated spaces



